This control mode may be configured to allow slow speed operation of the
motor.

Table 18 - Preset Slow Speed Parameters and Options

Basic Set-up

The Basic Set-up programming group provides a limited parameter set, allowing
quick start-up with minimal adjustments. If the user is planning to implement
some of the advanced features (i.e., Dual Ramp, Unbalance Level, etc.), then the
Linear List programming group should be selected. It provides all the Basic Setup
parameter set plus the advanced set.

Table 19 - Basic Set-up Parameters and Options

Parameter

Description

Option

Slow Speed Select

Allows the user to program the slow speed that best fits the application.

Low:

7%–Forward
10%–Reverse

High:

15%–Forward
20%–Reverse

Slow Speed Direction

This parameter programs the slow speed motor rotational direction.

Forward, Reverse

Slow Accel Current

Allows the user to program the required current to accelerate the motor to slow speed operation.

0...450% of full load current

Slow Running Current

Allows the user to program the required current to operate the motor at the slow speed setting.

0...450% of full load current

Parameter

Description

Option

SMC Option

Displays the type of controller. This is factory set and not adjustable.

Standard

Motor Connection

Displays the location of the SMC in relation to the motor windings.

Line or Delta

(4)

Line Voltage

Displays the system line voltage the unit is connected to.

MV Ratio

Scales the output from the Voltage Sensing Board to display correct line voltage.

1...1000
(see

Table 6 on page 58

Input Voltage

Ranges)

Starting Mode

Allows the user to program the SMC Flex controller for the type of starting that best fits the application.

Soft Start, Current Limit, Full Voltage,
Linear Speed

Ramp Time

This sets the time period during which the controller will ramp the output voltage.

0...30 s

Initial Torque

(1)

The initial reduced voltage output level for the voltage ramp is established and adjusted with this
parameter.

0...90% locked rotor torque

Current Limit Level

(2)

The current limit level that is applied for the Ramp time selected.

50...600% FLC

Kickstart Time

A boost current is provided to the motor for the programmed time period.

0.0...2.0 s

Kickstart Level

Adjusts the amount of current applied to the motor during kickstart.

0...90% locked rotor torque

Stop Input

Allows the user to select the operation of terminal 18, Stop Input.

Coast, Stop Option

Option 1 Input

Allows the user to select the operation of terminal 16, Option Input #1.

Disable, Stop Option, Fault, Fault NC,
Network

Option 2 Input

Allows the user to select the operation of terminal 15, Option Input #2.

Disable, Preset Slow Speed, Dual Ramp,
Fault, Fault NC, Network, Clear Fault,
Emergency Run

(5)

Stop Mode

Allows the user to program the SMC Flex controller for the type of stopping that best fits the application.

Soft Stop, Linear Speed

Stop Time

This sets the time period which the controller will ramp the voltage during a stopping maneuver.

0.0...120 s

CT Ratio

Scales the CT input to actual motor current (5 amp secondary assumed).
Example: CT Ratio = 150:5, program 150

1...1500