Publication 1797-6.5.6 - June 2005

1797-IBN16 FLEX Ex 16 NAMUR Input Module 24-3

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(-)

14.5 15

-

-

A, B, IIC

0.3

80.0

C, E, IIB

0.9

320.0

D, F, G, IIA

2.4

640.0

IMPORTANT

A terminal base may or may not have an I/O module
installed.

1797- IBN16

Allen-Bradley

B

-

A

7

PWR

6

5

4

3

2

1

0

9

8

11

10

13

12

15

14

6

16 Point NAMUR Input Module

6

FLEX Ex NAMUR
Input I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion