Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 157

Advertising
background image

Publication 1797-6.5.6 - June 2005

1797-IJ2 FLEX Ex Frequency Input Module 32-5

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

This module, 1797-IJ2, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.

The ambient operating temperature (T

amb

) for this product is -20°C to

70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when

mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Advertising