Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 155

Advertising
background image

Publication 1797-6.5.6 - June 2005

1797-IJ2 FLEX Ex Frequency Input Module 32-3

Table 1: Entity Values for Field Device Connections

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

6, 7;
9, 8;

23, 24
26, 25

14.7 15.0

-

-

A, B, IIC

0.62

80.0

C, E, IIB

1.82

320.0

D, F, G, IIA

4.96

640.0

1 and 2

Any one

channel

5, 3;

10, 12;
22, 20;

27, 29

14.7 10.0

-

-

A, B, IIC

0.62

150.0

C, E, IIB

1.82

600.0

D, F, G, IIA

4.96

1200.0

1 and 2

Any one

channel

5, 3, 6, 4;

10, 12, 9, 11;

22, 20, 21, 23;

27, 29, 26, 28

14.7 10.0

-

-

A, B, IIC

0.62

150.0

C, E, IIB

1.82

600.0

D, F, G, IIA

4.96

1200.0

1 and 2

Any one

channel

0, 2, 3;
1, 2, 3;

14, 12, 13;

15, 12, 13

26.5 82.0

-

-

A, B, IIC

0.095

2.0

C, E, IIB

0.285

8.0

D, F, G, IIA

0.76

16.0

Wiring

Method

Channel

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(mH)

1 and 2

Any one

channel

17, 18, 37

or

31, 32, 46

28

93.0

A, B, IIC

0.0

0.0

C, E, IIB

0.0

0.0

D, F, G, IIA

0.0

0.0

IMPORTANT

A terminal base may or may not have an I/O module
installed.

1797- IJ2

Allen-Bradley

B

-

A

7

PWR

6

5

4

3

2

1

0

1

2 Point Frequency Input Module

FLEX Ex Frequency
Input I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion

42066