![background image](/manuals/580372/41/background.png)
Publication 1797-6.5.6 - June 2005
1797-TB3 FLEX Ex Terminal Base Unit 3-3
Intrinsically Safe
Specifications
For a full list of specifications, refer to the FLEX Ex Terminal Base
Installation Instructions, publication 1797-5.1.
Terminals Assignments
+34, -35, +50, -51, and 96
pin
i
female I/O connector
pins
i
30-32, 62-64, 94-96
i
36, 49
All Other Terminals
Only for intrinsically safe circuits
U
i
<10V dc
I
i
<2.5A
C
i
< 1nF
L
i
Negligible
Must not be used for any connection
U
i
<30V dc
I
i
<100mA
C
i
<1nF
L
i
Negligible
Flexbus Connection Intrinsically Safe
U
i
<10V dc
I
i
<400mA
C
i
<1nF
L
i
Negligible
Operational Temperature
-20 to 70
o
C (-4 to 158
o
F)
Agency Certification
II 2G EEx ia IIC T4