Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 230

Advertising
background image

Publication 1797-6.5.6 - June 2005

50-4 1797-IJ2 FLEX Ex Frequency Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next
FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be
attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505. For additional information refer to
ANSI/ISA RP12.6.

This module, 1797-IJ2, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(

µH)

Male Bus

Connector

5.8

400

A-G

3.0

3.0

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(

µH)

Female Bus

Connector

5.8

400

A-G

2.64

0