Publication 1797-6.5.6 - June 2005

1797-PS1N FLEX Ex Power Supply 51-3

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

of the associated apparatus are less

than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 504 (Divisions) or 505 (Zones).

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 501 (Divisions).

Conduit runs must have sealing fittings at the entry of the enclosure.

Ch4
Ch3
Ch2

Ch1

1 2 3 4 5

17
16
15
14
13
12
11
10

Nonhazardous Location

Feed through
to next power
supply

85-250V ac
and 120-250V
dc power
supply

Hazardous (Classified) Location

Class I, Division 1 Groups A, B, C, D

Class II, Division 1 Groups E, F, G

Class III Division 1

Class 1, Zone1 IIC

nonintrinsically safe wiring

intrinsically safe wiring

To any FM approved device
with entity concept
parameters of (V

max

, I

max

,

C

i

, L

i

) appropriate for

connection to associated
apparatus with entity
concept parameters listed in
Table 1.

42487

Hazardous (Classified) Location

1797-PS1N

Class I, Division 1, Groups B, C, D

Class I, Zone 1, Group IIB + H2