Wiring to a 1797-tb3 or -tb3s terminal base unit, Intrinsically safe specifications, Connect wiring to the terminal base as shown below – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 70

Advertising
background image

Publication 1797-6.5.6 - June 2005

12-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input
Module Installation Instructions, publication 1797-5.4.

Row A

Row B

Row C

Ch 7

Ch 6

Ch 5

Ch 4

+V

CJC

-V

41505

Ch 7

+

L

Ch 2

Ch 1

Ch 0

Ch 3

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

H

-

+

L

H

-

+

L

H

-

+

L

H

-

+

L

H

-

+

L

H

-

+

L

H

-

+

L

H

-

-V

CJC

chassis
GND for
shield

chassis
GND for
shield

0+

0-

1-

1+

No connection allowed to terminals 36 and 49

+V

ATTENTION

Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.

Output (intrinsically safe)

(16 position male/female flexbus
connector)

U

i

< 5.8V

I

i

< 400mA

Li = Negligible
Ci < 1.35

µF

Power Supply

(+V, -V Intrinsically Safe)

U

i

< 9.5V dc

I

i

< 1A

L

i

= Negligible

C

i

= Negligible

Operational Temperature

-20 to +70

o

C (-4 to 158

o

F)

Agency Certification

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)

Certificates

DMT 98 ATEX E 023X