Chapter 44, 1797-ie8 flex ex 8 input analog module, Inputs – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 199: Wiring to a 1797-tb3 or -tb3s terminal base unit, Chapter, Connect wiring to the terminal base as shown below

Advertising
background image

1

Publication 1797-6.5.6 - June 2005

Chapter

44

1797-IE8 FLEX Ex 8 Input Analog Module

Inputs

Each input can be operated from an analog field device signal. Do not apply
any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a
common plus-line.

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT

When interconnecting several lines, you must consider the
total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+

-

+

-

+

-

+

-

Ch 7

Ch 6

Ch 5

Ch 4

+V -V

+V -V

40071

sig

sig

sig

sig

No connection
allowed

No connection
allowed

Ch 7

+

-

+

-

+

-

+

-

Ch 2

Ch 1

Ch 0

sig

sig

sig

sig

Ch 3

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

ATTENTION

Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.