1797-OB4D FLEX Ex 24V dc Non-Isolated
Source 4 Output Module

General Information

Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal
base unit.

Module Installation

Rotate keyswitch on terminal base unit clockwise to position 7 as required for
this type of module. Do not change the position of the keyswitch after
wiring the terminal base unit.

Outputs

Each output can operate a discrete field device. Do not apply any
non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020,
the European directives and regulations must be followed.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

40068

Row A

Row B

Row C

+

+

+

+

-

-

-

-

ch0

ch1

ch2

ch3

+V

+V

-V

-V

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37,
38, 39, 46, 47, 48, 49

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

Advertising