Intrinsically safe specifications, Fm input i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 228

Advertising
background image

Publication 1797-6.5.6 - June 2005

50-2 1797-IJ2 FLEX Ex Frequency Input Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Frequency Input Module
Installation Instructions, publication 1797-5.7.

FM Input I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

6, 7;
9, 8;

23, 24
26, 25

14.7 15.0

-

-

A, B

0.65

130.0

C, E

1.95

390.0

D, F, G

5.20

1040.0

1 and 2

Any one

channel

5, 3;

10, 12;
22, 20;

27, 29

14.7 10.0

-

-

A, B

0.65

300.0

C, E

1.95

900.0

D, F

5.20

2400.0

1 and 2

Any one

channel

5, 3, 6, 4;

10, 12, 9, 11;

22, 20, 21, 23;

27, 29, 26, 28

14.7 10.0

-

-

A

0.65

300.0

C, E

1.95

900.0

D, F, G

5.20

2400.0

1 and 2

Any one

channel

0, 2, 3;
1, 2, 3;

14, 12, 13;

15, 12, 13

26.5 82.0

-

-

A, B

0.13

4.5

C, E

0.39

13.5

D, F, G

1.04

36.0

Wiring

Method

Channel

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(mH)

1 and 2

Any one

channel

17, 18, 37

or

31, 32, 46

28

93.0

A, B

0

0

C, E

0

0

D, F, G

0

0