21-4 ControlNet Ex System

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system
diagram.

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

System Diagram Name

Catalog Number

Source

1797-RPA

1797-RPA

Allen-Bradley

RSD-CFA-Ex.CN

Pepperl+Fuchs

1797-RPFM

1797-RPFM

Allen-Bradley

RSD-FC-Ex2.CN

Pepperl+Fuchs

1797-ACNR15

1797-ACNR15

Allen-Bradley

RSD-GW-Ex2.CN

Pepperl+Fuchs

Coax Trunk Cable

1

1797-RG6

Allen-Bradley

3092A

2

Belden Wire & Cable Co.

3092A with blue jacket

Belden Wire & Cable Co.

ControlNet Ex Tap

1797-TPx

Allen-Bradley

RS-TPx-Ex

Pepperl+Fuchs

CNet Ex Trk Trm

1797-XT

Allen-Bradley

RS-XT-Ex

Pepperl+Fuchs

CNet Ex Tap Trm

1797-TCAP

Allen-Bradley

RS-TCAP-Ex

Pepperl+Fuchs

1

In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75

Ω ± 3Ω

Cable Capacitance = <5.94nF per 100m
Cable Resistance = >9.08

Ω per 100m

Cable Attenuation

0.2MHz > 0.93dB/100m

5MHz > 1.39dB/100m

(-20 to +70

o

C)

0.5MHz > 0.95dB/100m

10MHz > 1.86dB/100m

1MHz > 1.07dB/100m

20MHz > 2.73dB/100m

2MHz > 1.16dB/100m

50MHz > 4.33dB/100m

2

Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.