Intrinsically safe specifications, Ul, c-ul i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 164

Publication 1797-6.5.6 - June 2005
34-2 1797-PS2N2 FLEX Ex Power Supply
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Power Supply Installation
Instructions, publication 1797-5.12.
UL, C-UL I/O Entity
Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).
Table 1: Entity Values for Field Device Connections
Specifications
1797-PS2N2
Inset Voltage Range
19 to 32V dc
Operational
Temperature
-20 to 70
o
C (-4 to 158
o
F)
Agency Certification
Class I Division 1 Groups A, B, C, D
Class II Division 1 Groups E, F, G
Class III
Certificates
UL Certificate Number 99.19699
C
US
ATTENTION
Once power has been applied, wait 15 minutes after
disconnecting before opening cover.
Model
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(A)
Groups
C
a
(
µF)
L
a
(
µH)
PS2N2
1 and 2 Any one
channel
e.g. ch1
10(+), 11(-)
9.5
1.0
A, B
0.5
8
C, E
1.5
32
D, F, G
4.0
64