Intrinsically safe specifications, Ul, c-ul i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 164

Advertising
background image

Publication 1797-6.5.6 - June 2005

34-2 1797-PS2N2 FLEX Ex Power Supply

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Power Supply Installation
Instructions, publication 1797-5.12.

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Specifications

1797-PS2N2

Inset Voltage Range

19 to 32V dc

Operational
Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

Class I Division 1 Groups A, B, C, D

Class II Division 1 Groups E, F, G

Class III

Certificates

UL Certificate Number 99.19699

C

US

ATTENTION

Once power has been applied, wait 15 minutes after
disconnecting before opening cover.

Model

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(A)

Groups

C

a

(

µF)

L

a

(

µH)

PS2N2

1 and 2 Any one

channel
e.g. ch1

10(+), 11(-)

9.5

1.0

A, B

0.5

8

C, E

1.5

32

D, F, G

4.0

64