1797-BIC Bus Isolator Module and
1797-CEC Flexbus Connector
General Installation
The 1797-CEC and -BIC must not be exposed to the environment. These
modules have a protection factor of IP20. Provide a suitable metal enclosure.
If these modules are to be installed into a Zone 2 area, then ensure that this
enclosure has a protection class of IP54.
Make certain that you only connect the FLEX Ex backplane connector to
other intrinsically safe system modules to maintain the integrity of the
intrinsically-safe backplane.
QUALITY
B
-
A
Allen-Bradley
1797 - CEC
FLEXBUS
CONNECTOR
1
2
4
3
+V -V +V -V
1797 - BIC
PWR
QUALIT Y
B
-
A
Allen-Bradley
FLEXBUS
ISOLATOR
42864
1797-CEC
1797-BIC
ATTENTION
The 1797-BIC cannot be used as an associated apparatus
after its FLEX Ex backplane connector has been exposed
to non-intrinsically safe signals.