1797-BIC Bus Isolator Module and
1797-CEC Flexbus Connector

General Installation

The 1797-CEC and -BIC must not be exposed to the environment. These
modules have a protection factor of IP20. Provide a suitable metal enclosure.
If these modules are to be installed into a Zone 2 area, then ensure that this
enclosure has a protection class of IP54.

Make certain that you only connect the FLEX Ex backplane connector to
other intrinsically safe system modules to maintain the integrity of the
intrinsically-safe backplane.

QUALITY

B

-

A

Allen-Bradley

1797 - CEC

FLEXBUS

CONNECTOR

1

2

4

3

+V -V +V -V

1797 - BIC

PWR

QUALIT Y

B

-

A

Allen-Bradley

FLEXBUS

ISOLATOR

42864

1797-CEC

1797-BIC

ATTENTION

The 1797-BIC cannot be used as an associated apparatus
after its FLEX Ex backplane connector has been exposed
to non-intrinsically safe signals.