Publication 1797-6.5.6 - June 2005

32-4 1797-IJ2 FLEX Ex Frequency Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next
FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be
attached on a flexbus.

To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of V

oc

< 5.8V; I

sc

< 400mA.

To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V

oc

< 9.5V; I

sc

< 1A.

To any IS device with Entity
Concept parameters of
(V

max

, I

max

, C

i

, L

i

) appropriate for

connection to associated
apparatus with Entity
Concept parameters listed in
Table 2.

1797-IJ2

16

Shield Connection Only

50

51

35

34

V

max

=5.8V

I

max

=400mA

C

i

=2.64

µF

L

i

=0

V

max

=9.5V

I

max

=1A

C

i

=0

L

i

=0

Male Bus
Connector

33
40

41

42

43

44
45

0

Female Bus
Connector

1

2

3
4

5

6

7

8

9

10

11
12

13

14

15

20

21

22

23
24

25

26

27

28
29

V

max

=28V

I

max

=93mA

C

i

=0

L

i

=0

V

max

=28V

I

max

=93mA

C

i

=0

L

i

=0

17 18 37

31 32 46

To any intrinsically safe device
or associated apparatus with
Entity Concept parameters
of V

oc

< 28V; I

sc

< 93mA.

To any intrinsically safe device
or associated apparatus with
Entity Concept parameters
of V

oc

< 28V; I

sc

< 93mA.

ch0
Freq. In

ch1
Freq. In

ch0
Gate

ch1
Gate

Any Simple Apparatus or I.S.
device with Entity Concept
parameters (V

max

, I

max

, C

i

, L

i

)

appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1: Entity Values for Field

Any Simple Apparatus or I.S.
device with Entity Concept
parameters (V

max

, I

max

, C

i

, L

i

)

appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1: Entity Values for Field

42057

Hazardous (Classified) Location
Class I, Zone 0 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D
Class II, Div. 1 Groups E, F, G
Class III, Div. 1

Hazardous (Classified) Location
Class I, Zone 1 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class

III

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(

µH)

Male Bus

Connector

5.8

400

A-G

IIC, IIB, IIA

3.0

3.0

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(

µH)

Female Bus

Connector

5.8

400

A-G

IIC, IIB, IIA

2.64

0