Entity parameters example, Maximum input current (i, Or i – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 6: Maximum internal capacitance (c, Maximum internal inductance (l, And l, Also, the sum of all the u, And i, Cannot exceed the input u, 30v • i

Advertising
background image

Publication 1797-6.5.6 - June 2005

Preface 2

• maximum input current (I

i

or I

max

)

• maximum internal capacitance (C

i

)

• maximum internal inductance (L

i

)

In use, the sum of all the input C

i

and L

i

in a control loop cannot exceed the

C

o

and L

o.

Also, the sum of all the U

o

and I

o

cannot exceed the input U

i

and I

i

.

The following is a short explanation of how entity-based architectures help
simplify IS system design.

Entity Parameters Example

An output channel and the valve it will drive are illustrated in the following
figure. By comparing entity parameters, you can quickly determine the
appropriate match.

In this example, the combination is compatible because the valve can
withstand:

• U

i

= 30V

• I

i

= 165mA

These values are higher than what the 1797-IE8 can provide:

40052

cable length = 10m

268

21V

22

+

sig

C

i

<10pF/m

L

i

<0.5uH/m

R<0.1

Ω/m

P/I transmitter

EEx ia IIC T4

U

i

=30V

I

i

=165mA

C

i

=22.5nF

L

i

=730uH

Module

U

o

I

o

C

a

L

a

< or =
< or =
> or =
> or =

Total Loop

U

i

I

i

C

i

L

i

=
=
=
=

Transmitter

U

i

I

i

C

i

L

i

Distance

Cable

+

+

(length

*

C

i

per length)

(length

*

L

a

per length)

Module

U

o

<23.7V

I

o

<92.5mA

C

a

=66nF

L

a

=2.5mH

< or =
< or =
> or =
> or =

Total Loop

U

i

=30V

I

i

=165mA

C

i

=22.6nF

L

i

=735uH

=
=
=
=

Transmitter

U

i

=30V

I

i

=165mA

C

i

=22.5nF

L

i

=730uH

Distance

Cable

+

+

(10m

*

C

i

=10pF/m)

(10m

*

L

a

=0.5uH/m)

1797-IE8 Analog Input

EEx ia/ib IIB/IIC T4

U

o

<23.7V

I

o

<93.5mA

IIB

C

a

=560nF

L

a

=10mH

IIC

C

a

=66nF

L

a

=2.5mH