Inputs/outputs, Intrinsically safe specifications – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 245

Advertising
background image

Publication 1797-6.5.6 - June 2005

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector 55-3

Inputs/Outputs

Do not apply any non-intrinsically safe signals to the FLEX Ex backplane
connector.

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Bus Isolator Installation
Instructions, publication 1797-5.13.

1797-BIC Specifications

Output (Intrinsically Safe)

(16 pin male and female flexbus
connector)

V

t

<

5.75V dc

I

t

<

398.25mA

C

a

<

39.67uF

L

a

<

210uH

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

Nonincendive, use for Class I, Division 2
Groups A-D or Class I, Zone 2 Group IIC

Provides intrinsically safe outputs to Class I,
Division 1 Groups A-D or Class I, Zone 1
Group IIC

Certificates

FM Certificate Number 3010810

1797-CEC Specifications

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

Nonincendive, use for Class I, Division 2
Groups A-D or Class I, Zone 2 Group IIC

Certificates

FM Certificate Number 3010810

FM

FM

Advertising