Publication 1797-6.5.6 - June 2005

14-2 1797-PS1E FLEX Ex Power Supply

Typical Wiring
Configurations

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 85-250V AC In/Quad-Ex
DC Out Power Supply Installation Instructions, publication 1797-5.33.

42489

10

11 12 13

14

15

16

17

1

2

4

5

3

cha
GND

-

+

-

+

Vout

+V

-V +V -V

+V -V

+V

-V

Out 1

Out 2

Out 3

Out 4

Terminal Base Assignments

Vin

European AC Power Input

IS Power Output

Specifications

1797-PS1E (Series A)

1797-PS1E (Series B)

Inset Voltage Range

85 to 250V dc

Voltage U

O

<9.5V

Current I

O

<1A

C

o

(IIC)

<500 nF

L

o

(IIC)

<8

µH

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

EEx de [ib] IIC T4

II 2G EEx de [ib] IIC T4

II 3D IP54 T90°C

Certificates

BVS 98.D.2055X

DMT 02 ATEX E253 X

ATTENTION

Once power has been applied, wait 15 minutes after
disconnecting before opening cover.