Intrinsically safe specifications, Fm i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 224

Publication 1797-6.5.6 - June 2005
49-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input
Module Installation Instructions, publication 1797-5.4.
FM I/O Entity Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 1: Entity Values for Field Device Connections
Operational Temperature
-20 to +70
o
C (-4 to 158
o
F)
Agency Certification
Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4
Certificates
FM Certificate Number 3009806
FM
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2
Any one
channel
e.g. ch0
0(+), 1(H),
2(L), 3(-)
9.0
37.0
-
-
A, B
3.0
20.0
C, E
9.0
60.0
D, F, G
24.0
160.0
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
9.0
1.0
-
-
A, B
3.0
1000.0
C, E
9.0
1000.0
D, F, G
24.0 1000.0
0(+), 1(H),
2(L), 3(-)
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
-
-
9.0
38.0
A, B
3.0
20.0
C, E
9.0
60.0
D, F, G
24.0
160.0