Intrinsically safe specifications, Fm i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 224

Advertising
background image

Publication 1797-6.5.6 - June 2005

49-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input
Module Installation Instructions, publication 1797-5.4.

FM I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operational Temperature

-20 to +70

o

C (-4 to 158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

e.g. ch0

0(+), 1(H),

2(L), 3(-)

9.0

37.0

-

-

A, B

3.0

20.0

C, E

9.0

60.0

D, F, G

24.0

160.0

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

9.0

1.0

-

-

A, B

3.0

1000.0

C, E

9.0

1000.0

D, F, G

24.0 1000.0

0(+), 1(H),

2(L), 3(-)

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

-

-

9.0

38.0

A, B

3.0

20.0

C, E

9.0

60.0

D, F, G

24.0

160.0