Channel 0 gate input -5 channel 1 gate input -5, Channel 0 gate input, Channel 1 gate input – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 77

Publication 1797-6.5.6 - June 2005
1797-IJ2 FLEX Ex Frequency Input Module 13-5
Channel 0 Gate Input
Field devices may only be connected to the terminal of one of the three
following circuits. The terminals of the remaining two circuits must not be
connected.
Channel 1 Gate Input
Field devices may only be connected to the terminals of one of the three
circuits. The terminals of the remaining two circuits must not be connected.
Namur/Con
tact
(terminals
23-24)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 15mA
P
o
= 30mW
EEx ia
IIB
3.86
µF
300mH
2.6mH/
Ω
IIC
620nF
80mH
0.65mH/
Ω
Magnetic
500mV
(terminals
22-20)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 10mA
P
o
= 18mW
EEx ia
IIB
3.86
µF
600mH
4.15mH/
Ω
IIC
620nF
150mH
1.03mH/
Ω
Magnetic
50mV
(terminals
22-20,
23-21)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 10mA
P
o
= 18mW
EEx ia
IIB
3.86
µF
600mH
4.15mH/
Ω
IIC
620nF
150mH
1.03mH/
Ω
Namur/Con
tact
(terminals
26-25)
Protection
Group
Allowed
Capacitance
Allowed
Inductance
L
o
R
o
Ratio
U
o
= 14.7V
I
o
= 15mA
P
o
= 30mW
EEx ia
IIB
3.86
µF
300mH
2.6mH/
Ω
IIC
620nF
80mH
0.65mH/
Ω