Intrinsically safe specifications, Fm i/o entity parameters (each channel), Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 192: Operating temperature -20 to +70, C (-4 to +158, Wiring method channel terminals v, V) i, Ma) v, Ma) groups c, Μ f) l

Advertising
background image

Publication 1797-6.5.6 - June 2005

42-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module
Installation Instructions, publication 1797-5.7.

FM I/O Entity Parameters
(Each Channel)

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(-)

14.5 15

-

-

A, B

0.3

80.0

C, E

0.9

320.0

D, F, G

2.4

640.0

1797- IBN16

Allen-Bradley

B

-

A

7

PWR

6

5

4

3

2

1

0

9

8

11

10

13

12

15

14

6

16 Point NAMUR Input Module

6

FLEX Ex NAMUR
Input I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion

42060