13-2 1797-IJ2 FLEX Ex Frequency Input Module

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Frequency Input Module
Installation Instructions, publication 1797-5.7.

Row A

Row B

Row C

+V

-V

42334

3V

V+

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

6V

GND 50

mV

Sel

N

500/50

mV

8V

8V N

GND

6V

V+

3V

R0 NO R0 NC

-V

No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49

+V

R0 COM

R1 COM

50

mV

Sel

500/50

mV

Channel 0 Frequency Input

Channel 1 Frequency Input

GND

GND 50

mV

Sel

N

500/50

mV

8V

8V N

50

mV

Sel

500/50

mV

GND

R1 NO R1 NC

Channel 0 Gate Input

Channel 1 Gate Input

ATTENTION

Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.

Output (intrinsically safe)

(16 position male/female flexbus
connector)

U

o

< 5.8V

I

o

< 400mA

Li = Negligible
Ci < 2.64

µF

Power Supply

(+V, -V Intrinsically Safe)

U

i

< 9.5V dc

I

i

< 1A

L

i

= Negligible

C

i

= Negligible

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)

Certificates

DMT 98 ATEX E 033 X