Publication 1797-6.5.6 - June 2005

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 31-3

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

e.g. ch0

0(+), 1(H),

2(L), 3(-)

9.0

37.0

-

-

A, B, IIC

4.9

20.0

C, E, IIB

14.7

80.0

D, F, G, IIA

39.2

160.0

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

9.0

1.0

-

-

A, B, IIC

4.9

1000.0

C, E, IIB

14.7 1000.0

D, F, G, IIA

39.2 1000.0

0(+), 1(H),

2(L), 3(-)

37, 38, 39

(CJC0)

or

46, 47, 48

(CJC1)

-

-

9.0

38.0

A, B, IIC

4.9

20.0

C, E, IIB

14.7

80.0

D, F, G, IIA

39.2

160.0