Ul, c-ul i/o entity parameters, Ul, c-ul i/o entity parameters -3 – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 149

Publication 1797-6.5.6 - June 2005
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 31-3
UL, C-UL I/O Entity
Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).
Table 1: Entity Values for Field Device Connections
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2
Any one
channel
e.g. ch0
0(+), 1(H),
2(L), 3(-)
9.0
37.0
-
-
A, B, IIC
4.9
20.0
C, E, IIB
14.7
80.0
D, F, G, IIA
39.2
160.0
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
9.0
1.0
-
-
A, B, IIC
4.9
1000.0
C, E, IIB
14.7 1000.0
D, F, G, IIA
39.2 1000.0
0(+), 1(H),
2(L), 3(-)
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
-
-
9.0
38.0
A, B, IIC
4.9
20.0
C, E, IIB
14.7
80.0
D, F, G, IIA
39.2
160.0