Publication 1797-6.5.6 - June 2005

38-2 General FM Certification Information

I/O module capacitance value is cumulative. C

i (total)

= C

i (I/O module 1)

+

C

i (I/O module 2)

+ ... C

i (I/O module 8)

+ C

cable

(C

cable

= 100pf). C

i (total)

must be less than 30µF

(when the 1797-ACNR15 is used) or 39.67µF (when the 1797-BIC is used).
The limitation of 8 I/O modules per adapter is a functional limitation. Refer to
table 3 of the appropriate module for C

i

values. Note: Any combination of up

to eight FLEX Ex I/O modules meets this requirement. (This includes
1794-CE3, 1797-CE3, 1794-CE1, and 1797-CE1 cables.)

In any of the above diagrams, terminal bases without modules may be

connected.

This general FM certification information must be used in conjunction

with the appropriate module certification information.

Installation in Division 1/
Zone 1

Modules, adapters, and terminal base units must not be exposed to the
environment. Provide a suitable enclosure.

1

2

3

4

5

6

7

8

42488

connecting cable
1794-CE1 or -CE3

ATTENTION

Modules, adapters, and terminal base units cannot be used
in an intrinsically safe environment after they have been
exposed to non-intrinsically safe signals.