Publication 1797-6.5.6 - June 2005

43-2 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated Source
4 Output Module Installation Instructions, publication 1797-5.6.

FM I/O Entity Parameters

Wiring Methods

• Wiring method 1: Each channel is wired separately.
• Wiring method 2: Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(-)

27.4 110.0

-

-

A, B,

0.105 3.0

C, E

0.315 9.0

D, F, G

0.840 24.0

IMPORTANT

A terminal base may or may not have an I/O module
installed.

1797- OB4D

Allen-Bradley

B

-

A

0

1

2

3

4

5

6

7

PWR

7

4 Point Source Output Module

FLEX Ex Discrete
Output I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion

42058

Advertising