1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 12-3

CE/CENELEC I/O Entity
Parameters

Input circuits (+ to -) for ch0 to ch7 (terminals: 0-3; 4-7; 8-11; 12-15; 17-20;
21-24; 25-28; 29-32)

CJC circuits (+ to -) for CJC0 and CJC1 (terminals: 37, 39; 46, 48)

Input circuits (+ to -) for ch0 to ch7 and CJC circuits (+ to -) for CJC0 and
CJC1 (terminals 0-3, 37, 39; 4-7, 37, 39; 8-11, 37, 39; 12-15, 37, 39; 17-20, 37,
39; 21-24, 37, 39; 25-28, 37, 39; 29-32, 37, 39; 0-3, 46, 48; 4-7, 46, 48; 8-11, 46,
48; 12-15, 46, 48; 17-20, 46, 48; 21-14, 46, 48; 25-28, 46, 48; 29-32, 46, 48)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

/R

o

Ratio

U

o

= 9V

I

o

= 37mA

P

o

= 83mW

EEx ia

IIB

40

µF

80mH

1.7mH/

EEx ia

IIC

4.9

µF

20mH

0.4mH/

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

/R

o

Ratio

U

o

= 9V

I

o

= 1mA

P

o

= 3mW

EEx ia

IIB

40

µF

1H

63mH/

EEx ia

IIC

4.9

µF

1H

15mH/

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

/R

o

Ratio

U

o

= 9V

I

o

= 38mA

P

o

= 86mW

EEx ia

IIB

40

µF

80mH

1.7mH/

EEx ia

IIC

4.9

µF

20mH

0.4mH/