Chapter 26, 1797-ie8 flex ex 8 input analog module, General information – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 121: Module installation, Inputs, Wiring to a 1797-tb3 or -tb3s terminal base unit, Chapter, Connect wiring to the terminal base as shown below

Advertising
background image

1

Publication 1797-6.5.6 - June 2005

Chapter

26

1797-IE8 FLEX Ex 8 Input Analog Module

General Information

Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal
base unit.

Module Installation

Rotate keyswitch on terminal base unit clockwise to position 3 as required for
this type of module. Do not change the position of the keyswitch after
wiring the terminal base unit.

Inputs

Each input can be operated from an analog field device signal. Do not apply
any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a
common plus-line.

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT

When interconnecting several lines, you must consider the
total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+

-

+

-

+

-

+

-

Ch 7

Ch 6

Ch 5

Ch 4

+V -V

+V -V

40071

sig

sig

sig

sig

No connection
allowed

No connection
allowed

Ch 7

+

-

+

-

+

-

+

-

Ch 2

Ch 1

Ch 0

sig

sig

sig

sig

Ch 3

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

Advertising