And i, Or v, And l – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 118: Of the associated apparatus are greater than c, Respectively for the intrinsically safe apparatus, Terminals v, V) i, Ma) groups c, Μ f) l

Advertising
background image

Publication 1797-6.5.6 - June 2005

25-4 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Table 2: Flexbus Entity Values Which are Allowed for the Next
FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be
attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(

µH)

Male Bus

Connector

5.8

400

A-G

IIC, IIB, IIA

3.0

3.0

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(

µH)

Female Bus

Connector

5.8

400

A-G

IIC, IIB, IIA

1.35

0

Hazardous (Classified) Location
Class I, Zone 0 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D
Class II, Div. 1 Groups E, F, G
Class III, Div. 1

Hazardous (Classified) Location
Class I, Zone 1 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class

III

To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V

oc

< 5.8V; I

sc

< 400mA.

T

o any intrinsically safe

device or associated
apparatus with Entity
Concept parameters of
V

oc

< 9.5V; I

sc

< 1A.

To any IS device with Entity
Concept parameters of
(V

max

, I

max

, C

i

, L

i

) appropriate

for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.

1797-OB4D

16

Shield Connection Only

50

51

35

34

V

max

=5.8V

I

max

=400mA

C

i

=1350nF

L

i

=0

V

max

=9.5V

I

max

=1A

C

i

=0

L

i

=0

Male Bus
Connector

33
40

41

42

43

44
45

0 (+)

Female Bus
Connector

Any Simple Apparatus or I.S.
device with Entity Concept
parameters (V

max

, I

max

, C

i

, L

i

)

appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.

1 (-)

ch0

ch1

ch2

ch3

4 (+)
5 (-)

8 (+)
9 (-)

12 (+)
13 (-)

42059

Advertising