Chapter 31, 1797-irt8 flex ex thermocouple/rtd input module, General information – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 147: Module installation, Inputs

Advertising
background image

1

Publication 1797-6.5.6 - June 2005

Chapter

31

1797-IRT8 FLEX Ex Thermocouple/RTD
Input Module

General Information

Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal
base unit.

Module Installation

Rotate keyswitch on terminal base unit clockwise to position 2 as required for
this type of module. Do not change the position of the keyswitch after
wiring the terminal base unit.

Inputs

Each input can be operated from a thermocouple (TC) or resistance
temperature detector (RTD). Do not apply any non-intrinsically safe
signals to this module.

The channels in this module are electrically connected to each other and have a
common plus-line.

IMPORTANT

When interconnecting several lines, you must consider the
total accumulated power and check for intrinsic safety.

Advertising