Publication 1797-6.5.6 - June 2005

ControlNet Ex System 2-3

Describing the ControlNet
Ex System Diagram

A maximum of 48 ControlNet Ex

TM

nodes may be connected together by

250m of coax cable and 48 taps. The distance increases to 1000m when you
use only 2 taps. See the table below for more information.
The fiber media of the 1797-RPFM can be installed in a hazardous location
(Zone 0, 1 or 2) to connect two 1797-RPFM modules or they can be installed
through different locations into the non-hazardous location to connect the
1797-RPFM with any approved associated apparatus.
All cables and fiber media that are not light blue must be marked as IS using
the 1797-EXMK marking kit or other locally approved IS identification
and/or segregation method.
During the installation of the ControlNet Ex system, all metallic parts must be
isolated to prevent an earth connection (high voltage withstanding of isolating
material must be > 500V ac).

System
Diagram
Name

Catalog Number Catalog Name

Description

1797-RPA

1797-RPA

ControlNet Ex Modular
Repeater Adapter

Represents one ControlNet Ex node and
must be connected to a coax trunk cable
by
1797-TPx

1797-RPFM

1797-RPFM

ControlNet Ex Fiber
Repeater Module,
Medium Distance

Allows connection of a maximum of two
devices per 1797-RPA and is powered
directly by 1797-RPA

1797-ACNR15 1797-ACNR15

Redundant Media
ControlNet Ex Adapter

Represents one ControlNet Ex node and
must be connected to a coax trunk cable
by
1797-TPx -each one with two redundant
output channels that are connected to
different ControlNet Ex networks (coax
cables and 1797-TPx)

1797-BCNR

1797-BCNR

Redundant ControlNet
Ex Barrier

Allows connection between ControlNet and
ControlNet Ex networks

CNet Ex
Tap Trm

1797-TCAP

ControlNet Ex Tap
(Dummy) Terminator

Represents one ControlNet Ex node and is
a simple capacitor (56pF) with a coax
connector

ControlNet Ex
Tap

1797-TPx

ControlNet Ex Coax
Tap

Four types of connections available: S
(straight t-tap), R (right angle t-tap), YS
(straight y-tap), and YR (right angle y-tap)
- a maximum of 48 taps can be connected
together by coax trunk cable

CNet Ex
Trk Trm

1797-XT

ControlNet Ex Trunk
Terminator

Simple resistor (75

Ω) with coax connector

that must be on each end of the ControlNet
Ex coax trunk for termination

Coax Trunk
Cable

1786-RG6

Quad-Shield, RG-6
75

Ω Coax Trunk Cable

Maximum (functional) length between 2
1797-TPx is 3280ft (1000m) - each
1797-TPx reduces the (functional) coax
cable length by 53.4ft (16.3m)

None

None

Standard Coax Trunk
Cable BNC Couplers

Different standard cable couplers, 90

o

,

180

o

, etc.