Publication 1797-6.5.6 - June 2005

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 25-5

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1A, 20

µ

J, or 25mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.

This module, 1797-OB4D, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17-32, 36-39, and 46-49 shall not be

connected.

WARNING: Substitution of components may impair intrinsic safety.

AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.

The ambient operating temperature (T

amb

) for this product is -20°C to

70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when

mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.