Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 117
Advertising
Publication 1797-6.5.6 - June 2005
1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 25-3
Table 1: Entity Values for Field Device Connections
Wiring
Method
Channel Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(-)
27.4 110.0
-
-
A, B, IIC
0.03 2.0
C, E, IIB
0.09 8.0
D, F, G, IIA
0.24 16.0
IMPORTANT
A terminal base may or may not have an I/O module
installed.
1797- OB4D