Intrinsically safe specifications, Fm i/o entity parameters, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 206

Advertising
background image

Publication 1797-6.5.6 - June 2005

45-2 1797-IE8H FLEX Ex 8 Input HART Analog Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module
Installation Instructions, publication 1797-5.5.

FM I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(sig), 2(-) 24.4 92.5 -

-

A, B

0.12 4.0

C, E

0.35 12.0

D, F, G

0.95 32.0

1(sig), 2(-)

24.4 92.5 28

110

A, B

0.12 4.0

C, E

0.35 12.0

D, F, G

0.95 32.0

1797- IE8H

Allen-Bradley

B

-

A

7

PWR

0

1

2

3

4

5

6

8

8 CHANNEL ANALOG INPUT

FLEX Ex Analog
Input I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion