Intrinsically safe specifications, Fm i/o entity parameters – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 232

Advertising
background image

Publication 1797-6.5.6 - June 2005

51-2 1797-PS1N FLEX Ex Power Supply

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex Power Supplies Installation
Instructions, publication 1797-5.34.

FM I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Specifications

1797-PS1N

Voltage Range

85-250V ac or 120-250V dc

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

Mounting - Class I Division 1 Groups B-D T4

IS Power - Class I Division 1 Groups A-D T4
Class I Zone 1 AEx [ib] IIC

Certificates

FM Certificate Number 3009806

ATTENTION

Once power has been applied, wait 15 minutes after
disconnecting before opening cover.

FM

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(A)

Groups

C

a

(

µF)

L

a

(

µH)

1 and 2 Any one

channel
e.g. ch1

10(+), 11(-)

9.5

1.0

A, B

0.5

8

C, E

1.5

24

D, F, G

4.0

64

Advertising