1797-IE8 FLEX Ex 8 Input Analog Module 26-3

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(sig)

23.7 92.5 -

-

A, B, IIC

0.06 2.0

C, E, IIB

0.18 8.0

D, F, G, IIA

0.48 16.0

1(sig), 2(-)

5

1.0

-

-

A, B, IIC

100

1000

C, E, IIB

300

1000

D, F, G, IIA

800

1000

0(+), 1(sig), 2(-) -

-

23.7 93.5 A, B, IIC

0.06 2.0

C, E, IIB

0.18 8.0

D, F, G, IIA

0.48 16.0

IMPORTANT

A terminal base may or may not have an I/O module
installed.