Ul, c-ul i/o entity parameters, Ul, c-ul i/o entity parameters -3, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 123

Publication 1797-6.5.6 - June 2005
1797-IE8 FLEX Ex 8 Input Analog Module 26-3
UL, C-UL I/O Entity
Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).
Table 1: Entity Values for Field Device Connections
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(sig)
23.7 92.5 -
-
A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA
0.48 16.0
1(sig), 2(-)
5
1.0
-
-
A, B, IIC
100
1000
C, E, IIB
300
1000
D, F, G, IIA
800
1000
0(+), 1(sig), 2(-) -
-
23.7 93.5 A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA
0.48 16.0