Intrinsically safe specifications, Fm i/o entity parameters, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 236

Publication 1797-6.5.6 - June 2005
52-2 1797-PS2N2 FLEX Ex Power Supply
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Power Supply Installation
Instructions, publication 1797-5.12.
FM I/O Entity Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 1: Entity Values for Field Device Connections
Specifications
1797-PS2N2
Voltage Range
18 to 32V dc
Operational Temperature
-20 to 70
o
C (-4 to 158
o
F)
Agency Certification
Mounting - Class I Division 1 Groups B-D T4
IS Power - Class I Division 1 Groups A-D T4
Class I Zone 1 AEx [ib] IIC
Certificates
FM Certificate Number 3009806
ATTENTION
Once power has been applied, wait 15 minutes after
disconnecting before opening cover.
FM
PS2N PS2N2 PS2N PS2N2
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(A)
Groups
C
a
(
µF)
C
a
(
µF)
L
a
(
µH)
L
a
(
µH)
1 and 2 Any one
channel
e.g. ch1
10(+), 11(-)
9.5
1.0
A, B
0.8
0.5
10
8
C, E
2.4
1.5
30
24
D, F, G
6.4
4.0
80
64