Intrinsically safe specifications, Intrinsically safe specifications -2 – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 86

Advertising
background image

Publication 1797-6.5.6 - June 2005

17-2 1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Intrinsically Safe
Specifications

For a full list of specifications, refer to ControlNet Ex Modular Repeater
Adapter and Fiber Repeater Module, Medium Distance Installation
Instructions, publication 1797-5.15.

1797-RPA Specifications

ControlNet Ex BNC

Oscillation powered by:
U

o

< 5.4V dc

I

o

< 201mA

ac coupled with high-pass filter f > 500kHz

Output (intrinsically safe)

(30 pin male TTL bus connector)

Manufacturer specific bus
U

o

< 5.4V

I

o

< 201mA

P

o

< 1.09W

L

o

< 0.45

µH

C

o

< 71

µF

Power Supply

(+V, -V Intrinsically Safe)

U

i

< 9.5V dc

I

i

< 1A

P

i

< 9.5W

L

i

= Negligible

C

i

< 120nF

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

II (1) 2G EEx ia/ib IIB/IIC T4

Certificates

DMT 99 ATEX E 011 X

1797-RPM Specifications

Input (intrinsically safe)

(30 pin female TTL bus connector)

U

i

< 5.4V

I

i

< 201mA

P

i

< 1.1W

L

i

< 15

µH

C

i

< 41

µF

Output (intrinsically safe)

(30 pin male TTL bus connector)

U

o

< 5.4V

I

o

< 201mA

P

o

< 1.1W

L

o

< 0.45mH

C

o

< 71

µF

Fiber Optic Transmitter
Ch1 & Ch 2

Optical Peak Output Power
P optical < 1mW

Operational Temperature

-20 to 70

o

C (-4 to 158

o

F)

Agency Certification

II (1) 2G EEx ia/ib IIB/IIC T4

Certificates

DMT 99 ATEX E 011 X

Advertising