5-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module
Installation Instructions, publication 1797-5.7.

Row A

Row B

Row C

+V

-V

+V

-V

41504

+

-

Ch 0

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

+

-

Ch 1

+

-

Ch 2

+

-

Ch 3

+

-

Ch 4

+

-

Ch 5

+

-

Ch 6

+

-

Ch 7

+

-

Ch 8

+

-

Ch 9

+

-

Ch 10

+

-

Ch 11

+

-

Ch 12

+

-

Ch 13

+

-

Ch 14

+

-

Ch 15

No connection allowed to terminals 36 and 49

ATTENTION

Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.

Output (intrinsically safe)

(16 position male/female flexbus
connector)

U

i

< 5.8V

I

i

< 400mA

Li = Negligible
Ci = Negligible

Power Supply

(+V, -V Intrinsically Safe)

U

i

< 9.5V dc

I

i

< 1A

L

i

= Negligible

C

i

= Negligible

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)

Certificates

DMT 98 ATEX E 013 X