Publication 1797-6.5.6 - June 2005

37-2 1797-BCNR Redundant ControlNet Ex Barrier

Intrinsically Safe
Specifications

The ControlNet Ex barrier type 1797-BCNR is an associated apparatus
according to EN 50020. If the ControlNet Ex barrier is connected to
intrinsically-safe circuits, the applicable national and local construction,
installation, and operating regulations must be heeded (in Germany DIN EN
50020, DIN VDE 0165).

For a full list of specifications, refer to Redundant ControlNet Barrier
Installation Instructions, publication 1797-5.1x.

Repair

The ControlNet Ex barrier is not field-repairable. Any attempt to open this
device will void the warranty and IS certification. If repair is necessary, return
this device to the factory.

1797-BCNR Specifications

IS Output
(BNC Connector in Blue Area)

Maximum open circuit voltage U

o

is 7V

Maximum current I

o

is 14mA (at the resonant

frequency of 66kHz)

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

II (2) G [EEx ib] IIC

Certificates

DMT 99 ATEX E xxx X

0102