48-2 1797-OE8H FLEX Ex 8 Output HART Analog Module
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex 8 Output Analog Module
Installation Instructions, publication 1797-5.3.
FM I/O Entity Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 1: Entity Values for Field Device Connections
Operational Temperature
-20 to +70
o
C (-4 to +158
o
F)
Agency Certification
Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4
Certificates
FM Certificate Number 3009806
FM
Wiring
Method
Channel
Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(sig)
21.0 100.0 -
-
A, B
0.20 3.5
C, E
0.60 10.5
D, F, G
1.60 28.0
1797- OE8H
Allen-Bradley
B
-
A
OUT 1
OUT 0
OUT 2
PWR
OUT 7
OUT 6
OUT 5
OUT 4
OUT 3
4
8 CHANNEL ANALOG OUTPUT
FLEX Ex Analog
Output I/O Module
LEDs
Female Bus
Connection
Field Wiring
Terminals
Terminal
Base
Terminal
Base Key
Male Bus
Connection
Key Position for
Terminal Base
Insertion
42013