Intrinsically safe specifications, Fm i/o entity parameters, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 220

Advertising
background image

Publication 1797-6.5.6 - June 2005

48-2 1797-OE8H FLEX Ex 8 Output HART Analog Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module
Installation Instructions, publication 1797-5.3.

FM I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC).

Table 1: Entity Values for Field Device Connections

Operational Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4

Certificates

FM Certificate Number 3009806

FM

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2 Any one

channel
e.g. ch0

0(+), 1(sig)

21.0 100.0 -

-

A, B

0.20 3.5

C, E

0.60 10.5

D, F, G

1.60 28.0

1797- OE8H

Allen-Bradley

B

-

A

OUT 1

OUT 0

OUT 2

PWR

OUT 7

OUT 6

OUT 5

OUT 4

OUT 3

4

8 CHANNEL ANALOG OUTPUT

FLEX Ex Analog
Output I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal
Base

Terminal
Base Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion