Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 36

Publication 1797-6.5.6 - June 2005
2-4 ControlNet Ex System
Certified Equivalent ControlNet Ex System Diagram Items
You may use these items as equivalents for the items shown on the system
diagram.
System Diagram Name
Catalog Number
Source
1797-RPA
1797-RPA
Allen-Bradley
RSD-CFA-Ex.CN
Pepperl+Fuchs
1797-RPFM
1797-RPFM
Allen-Bradley
RSD-FC-Ex2.CN
Pepperl+Fuchs
1797-ACNR15
1797-ACNR15
Allen-Bradley
RSD-GW-Ex2.CN
Pepperl+Fuchs
1797-BCNR
1797-BCNR
Allen-Bradley
RS-FB-Ex2.CN
Pepperl+Fuchs
Coax Trunk Cable
1
1786-RG6
Allen-Bradley
3092A
2
Belden Wire & Cable Co.
3092A with blue jacket
Belden Wire & Cable Co.
ControlNet Ex Tap
1797-TPx
Allen-Bradley
RS-TPx-Ex
Pepperl+Fuchs
CNet Ex Trk Trm
1797-XT
Allen-Bradley
RS-XT-Ex
Pepperl+Fuchs
CNet Ex Tap Trm
1797-TCAP
Allen-Bradley
RS-TCAP-Ex
Pepperl+Fuchs
1
In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75
Ω ± 3Ω
Cable Capacitance = <5.94nF per 100m
Cable Resistance = >9.08
Ω per 100m
Cable Attenuation
0.2MHz > 0.93dB/100m
5MHz > 1.39dB/100m
(-20 to +70
o
C)
0.5MHz > 0.95dB/100m
10MHz > 1.86dB/100m
1MHz > 1.07dB/100m
20MHz > 2.73dB/100m
2MHz > 1.16dB/100m
50MHz > 4.33dB/100m
2
Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.