Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 36

Advertising
background image

Publication 1797-6.5.6 - June 2005

2-4 ControlNet Ex System

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system
diagram.

System Diagram Name

Catalog Number

Source

1797-RPA

1797-RPA

Allen-Bradley

RSD-CFA-Ex.CN

Pepperl+Fuchs

1797-RPFM

1797-RPFM

Allen-Bradley

RSD-FC-Ex2.CN

Pepperl+Fuchs

1797-ACNR15

1797-ACNR15

Allen-Bradley

RSD-GW-Ex2.CN

Pepperl+Fuchs

1797-BCNR

1797-BCNR

Allen-Bradley

RS-FB-Ex2.CN

Pepperl+Fuchs

Coax Trunk Cable

1

1786-RG6

Allen-Bradley

3092A

2

Belden Wire & Cable Co.

3092A with blue jacket

Belden Wire & Cable Co.

ControlNet Ex Tap

1797-TPx

Allen-Bradley

RS-TPx-Ex

Pepperl+Fuchs

CNet Ex Trk Trm

1797-XT

Allen-Bradley

RS-XT-Ex

Pepperl+Fuchs

CNet Ex Tap Trm

1797-TCAP

Allen-Bradley

RS-TCAP-Ex

Pepperl+Fuchs

1

In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75

Ω ± 3Ω

Cable Capacitance = <5.94nF per 100m
Cable Resistance = >9.08

Ω per 100m

Cable Attenuation

0.2MHz > 0.93dB/100m

5MHz > 1.39dB/100m

(-20 to +70

o

C)

0.5MHz > 0.95dB/100m

10MHz > 1.86dB/100m

1MHz > 1.07dB/100m

20MHz > 2.73dB/100m

2MHz > 1.16dB/100m

50MHz > 4.33dB/100m

2

Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.

Advertising