Publication 1797-6.5.6 - June 2005

44-4 1797-IE8 FLEX Ex 8 Input Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next
FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be
attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

or V

t

and I

t

of the associated apparatus

are less than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores

more than 1.2V, 0.1A, 20µJ, or 25mW.

Terminals

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(

µH)

Male Bus

Connector

5.8

400

A-G

3.0

3.0

Terminals

V

max

(V)

I

max

(mA)

Groups

C

i

(

µF)

L

i

(

µH)

Female Bus

Connector

5.8

400

A-G

1.35

0

Hazardous (Classified) Location
Class I, Zone 0 Group IIC
Class I, Div. 1 Groups A, B, C, D
Class II, Div. 1 Groups E, F, G
Class III, Div. 1

Hazardous (Classified) Location
Class I, Zone 1 Group IIC
Class I, Div. 1 Groups A, B, C, D

For connection to other
modules, refer to the General
FM Certification Information
on page 38-1.

1797-IE8

16

Shield Connection Only

50

51

35

34

V

max

=5.8V

I

max

=400mA

C

i

=1350nF

L

i

=0

V

max

=9.5V

I

max

=1A

C

i

=0

L

i

=0

Male Bus
Connector

33
40

41

42

43

44
45

0 (+)

Female Bus
Connector

Any Simple Apparatus or FM
approved device with Entity
Concept parameters (V

max

, I

max

,

C

i

, L

i

) appropriate for connection

to associated apparatus with
Entity Concept parameters listed
in Table 1: Entity Values for Field

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)

5 (sig)
6 (-)
8 (+)

9 (sig)
10 (-)

12 (+)

13 (sig)
14 (-)

17 (+)

18 (sig)
19 (-)

21 (+)

22 (sig)
23 (-)
25 (+)

26 (sig)
27 (-)

29 (+)

30 (sig)
31 (-)

42056

For connection to other
modules, refer to the General
FM Certification Information
on page 38-1.

From FM approved devices,
1797-PS1N, -PS2N, or
-PS2N2.

Advertising