Publication 1797-6.5.6 - June 2005

55-2 1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

I/O module capacitance value is cumulative. Ci (total) = Ci (I/O module 1) + Ci

(I/O module 2) + ...Ci (I/O module 8). Ci (total) must be less than 39.67

µ

F. The

limitation of eight I/O modules per isolator is a functional limitation. The Ci values
referred to here are for the female bus connector of the I/O modules and may be
found in the appropriate I/O module block diagram.

Isolator

Restriction

1797-BIC and -CEC

Maximum of 8 I/O modules

1794

Adapter

1797

CEC

1797

BIC

1797 I/O

& Base

1797 I/O

& Base

1797 I/O

& Base

1797 I/O

& Base

1797

power

supply

24V dc

power

supply

42754

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Nonhazardous or Hazardous
(Classified) Location
Class I, Zone 2, Group IIC or
Class I, Division 2, Groups A-D

Nonhazardous or Hazardous
(Classified) Location
Class I, Zone 1, Group IIC or
Class I, Division 1, Groups A-D

42876

Diagram 1

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Nonhazardous or Hazardous
(Classified) Location
Class I, Zone 2, Group IIC or
Class I, Division 2, Groups A-D

Nonhazardous or Hazardous
(Classified) Location
Class I, Zone 1, Group IIC or
Class I, Division 1, Groups A-D

42877

Diagram 2