Intrinsically safe specifications, Ul, c-ul i/o entity parameters, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 144

Advertising
background image

Publication 1797-6.5.6 - June 2005

30-2 1797-OE8H FLEX Ex 8 Output HART Analog Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module
Installation Instructions, publication 1797-5.3.

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

ATTENTION

Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates

UL Certificate Number 99.19699

C

US

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

e.g. ch0

0(+), 1(-)

21.0 100.0

-

-

A, B, IIC

0.08 2.0

C, E, IIB

0.24 8.0

D, F, G, IIA

0.64 16.0

Advertising