Intrinsically safe specifications, Ul, c-ul i/o entity parameters, Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual

Page 140

Advertising
background image

Publication 1797-6.5.6 - June 2005

29-2 1797-OE8 FLEX Ex 8 Output Analog Module

Intrinsically Safe
Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module
Installation Instructions, publication 1797-5.3.

UL, C-UL I/O Entity
Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature

-20 to +70

o

C (-4 to +158

o

F)

Agency Certification

Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates

UL Certificate Number 99.19699

C

US

Wiring

Method

Channel

Terminals

V

oc

(V)

I

sc

(mA)

V

t

(V)

I

t

(mA)

Groups

C

a

(

µF)

L

a

(mH)

1 and 2

Any one

channel

e.g. ch0

0(+), 1(-)

21.0 100.0

-

-

A, B, IIC

0.08 2.0

C, E, IIB

0.24 8.0

D, F, G, IIA

0.64 16.0