Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

101

Communication

Passwords
This section provides access to perform password administration. Administrator level access is
required. There are three standard levels of access provide by the controller: User (Read Only),
Super-User (Read/Write without password administration capabilities, and Administrator
(Read/Write with password administration capabilities). The controller also has the ability to
management User names and assigned passwords. Passwords can be up to 15 characters. Sample
screens for both are shown below.


Security

This section provides the ability to establish various phone numbers over traditional
telephone line connection for alarm calls. Also contained in this section are a couple of
plant level features.


Emergency Power
Off Enable (EPO)

If enabled, the remote Emergency Power Off (EPO) feature allows the
controller to detect the occurrence of a contact closure and force open
all battery contactors in the system. The battery contactor will open
five seconds after the contact has been asserted. Once the contact is
removed, the battery contactor will be re-asserted to its previous
operational state. The factory default for this feature is Disabled.

Remote Rectifier In
Standby

Provides the ability to disable or enable the capability of placing a
rectifier into Standby operation through remote means such as the
network, modem, or local Craft port.

Network
The Pulsar Edge supports network access to almost all controller functions including all voltage
and temperature readings, current alarms, and alarm history. It supports a web-based user