GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 154

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

154

CNT- Disconnect Contactor Control

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

2= “VOLTAGE+TIME”

cnx,dtm

Disconnect remaining time

number

>0 means going to
disconnect

cnx,rth

Reconnect threshold

number

19.5-27V or 39-55V

cnx,rdy

Reconnect delay

number

0-300 seconds

cnx,ram

Reconnect automode

text

0=“NONE”
1=“VOLTAGE”
2=“VOLTAGE+TIME”

cnx 4,rtm

Reconnect remaining time

number

>0 means going to reconnect

The contactors are identified as follows:
CN1 = Battery Disconnect (LVBD1)
CN2 = Load 1 Disconnect (LVLD1)
CN3 = Load 2 Disconnect (LVLD2)
CN4 = Load 3 Disconnect (LVLD3)

DCM- Distribution Current Monitor

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

dcmxx,ide

Identifier

number

DCMC1 is the plant shunt
DCM01-DCM08

dcmxx,des

Description

number

Contactor 1

dcmxx,sn

Serial Number

text

Serial number

dcmxx,brc

Board Code

text

Board code

dcmxx,stt

State

text

NONE
MISSING
PRESENT

dcmxx,typ

Shunt Type

text

NONE
LOAD
BATTERY

dcmxx,val

Reading

number

ddd.d Amps

dcmxx,sha

Shunt amp rating

number

0-9999 Amps

The shunt type defaults are as follows:
DCMC1 = Battery
DCM01 = Battery
DCM02-DCM08 = Load

DCN- Distribution Contactor Interface

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

dcnxx,ide

Identifier

number

DCN01-DCN06

dcnxx,des

Description

number

Contactor 1

dcnxx,sn

Serial Number

text

Serial number

dcnxx,brc

Board Code

text

Board code

dcnxx,stt

State

text

NONE
MISSING
OPEN
CLOSED

dcnxx,typ

Contactor interface type

text

NONE, CN1, CN2, CN3, or
CN4