Specifications – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 20

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

20

Specifications

Table 2-2: Pulsar Edge Controller Specifications

General

Item

Specification

Input Voltage Ranges (power)

48V: 36.5 volts to 60 volts
24V: 18.5 volts to 32 volts

Input Power

5.0 watts maximum

Input Power Connections

Shelf powered. No external connection required;

Front Panel Interface

─ Asynchronous RS232 or USB Craft Port
─ Two status LEDs
─ Options with LCD Interface

System Configuration Methods

─ Front panel Craft port with T1.317 or EasyView2
─ 10/100 Base-T port
─ Serial port with external MODEM option

Maximum Number Of Power Units

─ 12 CP, 6 SPS-EPs, 32 NEs, 24 QS in ID mode
─ Many more in ID override mode (app dependent)

Low-Voltage Disconnects

─ Up to eight remote LVD contactors with 3

independent configurable Load disconnect
thresholds (LVLDs) and 1 configurable Battery
disconnect threshold (LVBD)

─ Integrated control/monitor capability for single

LVD with remote distribution control modules

Temperature Monitoring

─ Up to 16 One-Wire battery temperature probes
─ Controller ambient sensor built into LCD display

System Inputs/Outputs

Alarm and Control Inputs

─ Six configurable system alarm inputs of the

closure/open to “VBus-“ or -48V

─ *Up to 9 customer inputs of the closure/open to

return type

Alarm Contact Outputs

*Up to 6 User configurable Form-C Outputs

Alarm Contact Ratings

60 VDC, 0.5A

Plant Voltage Measurement
Accuracy

0 to 50°C (±0.05% of full scale + 1 count)

-40 to 75°C (±0.1% of full scale + 1 count)

Resolution



48V Systems: ±40 mV; 24V Systems: ±25 mV
48V Systems: ±70 mV; 24V Systems: ±40 mV
0.01V

*Depends on factory hardware configuration of controller and if the alarm contacts are present.