Factory Default

Factory 24V

Rectifier Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Group Standby/Sequencing Enable

1=Enabled

0=Disabled

0

DC1,RSQ

Remote rectifier Off Enable

1=Enabled

0=Disabled

1

PS1,RRF

Rectifier Redundancy Threshold

1 to 80

1

RLS1,THR

Multiple Rectifier Fail

2 to 88

2

MFA1,THR

Oring FET test enable

1=Enabled

0=Disabled

1

GM1,OFT

Efficiency Enable

1=Enabled

0=Disabled

0

DC1,EME

Efficiency Target

20% to 95%

70

DC1,EMT

Efficiency Rectifier Turn On
Threshold

25% to 100%

76

DC1,EMO

Efficiency initial delay

1 to 30 minutes

10

DC1,EMI

Efficiency Inter-Rectifier delay

1 to 30 minutes

10

DC1,EMW

Walk-In Enable

1=Enabled

0=Disabled

1

GM1,WIE

Converter Current Limit

30 to 100%

100

CP1,CLM

Converters

Converter Redundancy Loss Enable

1=Enabled

0=Disabled

1

CP1,RME

Remote converter Off Enable

1=Enabled

0=Disabled

0

CP1,ROF

Low Voltage Disconnect Input
Threshold

20.0 to 25.0V
40.0 to 50.0V

23.0

46.0

CP1,DTH

Low Voltage Reconnect Input
Threshold

22.0 to 27.0V
44.0 to 54.0V

25.0

50.0

CP1,RTH

Low Voltage Disconnect Enable

1=Enabled

0=Disabled

0

CP1,LVD

Converter Redundancy Threshold

1 to 32

1

CRL1,THR

Multiple Converter Fail

2 to 8

2

CMFA1,THR

Battery

Discharge Test

Timed Test Duration

0:0:0 to 23:59:59

2:00:00

BR1,TMD

Automatic Battery Test Feature

disabled, 20%,

timed, Ah Out

"disabled"

BR1,BTE

Automatic Test (AT) Interval

1 to 18 Months

12

BR1,TIN

Date For Next Automatic Test

yyyy-mm-dd

1/1/2099

BR1,ATD

Start Time For Automatic Test

0 to 23

0

BR1,ATH

Hours To Wait From Last BD
Before AT

0 to 240 hours

72

BR1,ATW

Manual Test Type

disabled, 20%,

timed, Ah Out

"20%"

BR1,MTT

Battery test Ah to be removed

10-1000Ah

10

BR1,AHO

Reserve Time Low (Full Capacity)

00:00 to 99:59

00:00

RTL1,THR

Real-time Reserve Low (During
BD)

00:00 to 99:59

00:00

RRTL1,THR

Battery Boost

Boost Maximum Duration

1 to 80 Hours

1

BS1,TMD

Automatic Boost Feature

disabled, timed,

or current

"disabled"

BS1,ATM

Auto Boost BD Multiplication
Factor

0.1 to 9.0

0.5

BS1,AMF

Auto Boost Termination Current
Threshold

1 to 999A

5

BS1,CTA

Shunt Monitors

Plant Shunt Type

Battery/None

/Load

"BATTERY"

DCMC1,TYP

Plant Shunt Current Rating

0 to 9999 Amps

100

DCMC1,SHA

ID1 Type

Battery/None

/Load

"BATTERY"

DCM01,TYP