Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

186

Factory Default

Factory 24V

Rectifier Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

ID1 Shunt Current Rating

0 to 9999 Amps

100

DCM01,SHA

ID2 Type

Battery/None

/Load

"NONE"

DCM02,TYP

ID2 Shunt Current Rating

0 to 9999 Amps

100

DCM02,SHA

ID3 Type

Battery/None

/Load

"NONE"

DCM03,TYP

ID3 Shunt Current Rating

0 to 9999 Amps

100

DCM03,SHA

ID4 Type

Battery/None

/Load

"NONE"

DCM04,TYP

ID4 Shunt Current Rating

0 to 9999 Amps

100

DCM04,SHA

ID5 Type

Battery/None

/Load

"NONE"

DCM05,TYP

ID5 Shunt Current Rating

0 to 9999 Amps

100

DCM05,SHA

ID6 Type

Battery/None

/Load

"NONE"

DCM06,TYP

ID6 Shunt Current Rating

0 to 9999 Amps

100

DCM06,SHA

ID7 Type

Battery/None

/Load

"NONE"

DCM07,TYP

ID7 Shunt Current Rating

0 to 9999 Amps

100

DCM07,SHA

ID8 Type

Battery/None

/Load

"NONE"

DCM08,TYP

ID8 Shunt Current Rating

0 to 9999 Amps

100

DCM08,SHA

All Load Shunts Monitored

1=Enabled

0=Disabled

0

DC1,MLS

Built-in Inputs

Input 1 Description

<=32 chars

"Fuse Alarm Major"

IN001,DES

Input 1 Type

"FAJ1"

IN001,TYP

Input 1 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN001,POL

Input 2 Description

<=32 chars

"Open String"

IN002,DES

Input 2 Type

"OSA"

IN002,TYP

Input 2 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN002,POL

Input 3 Description

<=32 chars

"Auxiliary Major Alarm"

IN003,DES

Input 3 Type

"AMJ"

IN003,TYP

Input 3 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN003,POL

Input 4 Description

<=32 chars

"Air Conditioner Fail"

IN004,DES

Input 4 Type

"AUX1"

IN004,TYP

Input 4 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN004,POL

Input 5 Description

<=32 chars

"Door Open"

IN005,DES

Input 5 Type

"AUX2"

IN005,TYP

Input 5 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN005,POL

Input 6 Description

<=32 chars

"SPD Fail"

IN006,DES

Input 6 Type

"AUX3"

IN006,TYP

Input 6 Active State

CLOSED=Battery

OPEN=No BAT

"CLOSED"

IN006,POL

Input 7 Description

<=32 chars

"PBT/TR"

IN007,DES

Input 7 Type

""

IN007,TYP

Input 7 Active State

CLOSED=Closed

to RTN,

OPEN=Open to

RTN

"CLOSED"

IN007,POL

Input 8 Description

<=32 chars

"High External Ambient"

IN008,DES